DC 10000

 

 

DC 10000 

DC 10000 HA

Cooling capacity

3000 Watt – 10000 BTU

3000 Watt – 10000 BTU

Power consumption

672 Watt 24 or 48 VDC

770 Watt 24 or 48 VDC

Size mm

Size inches

700 W x 350D  x 1000H

27,5W x 13,0D x 40,0 H

700 W x 350D  x 1000H

27,5W x 13,0D x 40,0 H

Weight

70kg / 152 lbs

72kg / 155 lbs

Max. outdoor ambient

45 ºC / 113 ºF

55 ºC / 131 ºF

Low voltage settings

(Unit will shut down if there is a low voltage)

24 VDC = 21,5 volt

48 VDC = 43,0 volt

24 VDC = 21,5 volt

48 VDC = 43,0 volt

Restart settings

(If there was a low voltage the unit will restart at)

24 VDC = 26,0 volt

48 VDC = 52,0 volt

24 VDC = 26,0 volt

48 VDC = 52,0 volt

High pressure switch

24 bar

24 bar

Low pressure switch

2 bar

2 bar

Safety switches

Max. temperature compressor and motor

Max. temperature compressor and motor

Coolant/ refrigerant

R134a

R134a

Brochure

User manual

Photo gallery
 

DC 10000 HA

 
   

 

 

 


DC Airco telecom products are availably in 24 and 48 vdc.
The first product in this series was developed to work if there is a power black out.
Now days there are sites where the customer removes the normal grid air conditioners and replace them with
DC 10000’s because of its total energy consumption and its ability to work from the battery bank.
In other cases the site is turn in to a solar/wind energy drive site or to save fuel
and reduce running hours of the generators the 230/115 volt driven Air conditioners are replaced by the DC10000.
G
 

DC Airco type 10000 is designed specially to cool telecom shelters and other enclosures  in remote area’s 
Introduced in 2002 to work as a back up system when the grid as a power failure.
It is now days used in different settings, as fuel saver on generator driven cell sites,  on solar and wind energy,
or as energy saver and back up system on sites with a normal 230/115 volt AC grid connection.
This product is used in parts of Africa, southern Europe, Caribbean, and Australia at temperatures till 45 degrees Celsius (113°F)

 

 

Generator powered BTS stations

With replacing the existing 230 VAC Air Conditioners by DC Airco units the
running hours og the gensets can be reduced from 24/7 till less than 10 hours a day.

(1) payback in less than 5 months.
(2) less pollution.


       
 

Grid powered BTS stations

With replacing the 230 or 380 VAC Air Conditioners for DC Airco units
the station keeps on working during power outages and unstable grid.

(1) no backup generator needed.
(2) no interruted service for the subscriber.
(3) less energy cosumption.

 

 

       
 

Remote BTS stations

Using DC Airco units makes it possible to run the station
on solar and/or wind energy. Depending on the location.

(1) no fuel consumption.
(2) no pollution.